- Aaccording to EN/IEC standard 60947 – 2, suitable for protection of commercial and middle power installations. Rated insulation voltage of 500V. Rated impulse withstand voltage of 6kV.
- Compliat with NEMA AB‐1. Climatic condition according to IEC/EN 60947 – 1 Annex Q, Cat. F subject to temperature, humidity, vibration, shock and salt mist.
- Protection unit with LCD screen for regulation of thermal and magnetic currents. Thermal regulation within range of 140A – 240A. Magnetic regulation within range of 600A.Equipped with earth leakage module with LCD screen. Earth leakage trip integrated of type A, with adjustable sensitivity of 0,03 ‐ 0,3 ‐ 1 ‐ 3 Ampere and adjustable tripping of 0 ‐ 0,3 ‐ 1 ‐ 3 seconds
- Can be equipped with releases (undervoltage and shunt releases) and auxiliary contacts. Can used with rotary handles or motor operator. Locking accessories are available.
- Has diffent type of possible connection accessories: cage terminals, spreader and rear terminals. Is available also in a plug-in version (circuit breaker fitted with special terminals and mounted on a plug-in base)
The + product
- Possibility of DIN mounting and full accessory range.