技術規格
Download Product Datasheet
Main
range of product |
Modicon TM3
|
|
product or component type |
Discrete I/O module
|
|
range compatibility |
Modicon M251 Modicon M241 Modicon M221
|
|
discrete input number |
4 for input conforming to IEC 61131-2 Type 1
|
|
discrete input logic |
Sink or source (positive/negative)
|
|
discrete input voltage |
24 V
|
|
discrete input current |
7 mA for input
|
|
discrete output type |
Relay normally open
|
|
discrete output number |
4
|
|
discrete output logic |
Positive or negative
|
|
discrete output voltage |
24 V DC for relay output 240 V AC for relay output
|
|
discrete output current |
2000 mA for relay output
|
|
Complementary
discrete I/O number |
8
|
|
current consumption |
5 mA at 5 V DC via bus connector (at state off) 0 mA at 24 V DC via bus connector (at state on) 0 mA at 24 V DC via bus connector (at state off) 25 mA at 5 V DC via bus connector (at state on)
|
|
discrete input voltage type |
DC
|
|
voltage state 1 guaranteed |
15...28.8 V for input
|
|
current state 1 guaranteed |
>= 2.5 mA (input)
|
|
voltage state 0 guaranteed |
0...5 V for input
|
|
current state 0 guaranteed |
<= 1 mA (input)
|
|
input impedance |
3.4 kOhm
|
|
response time |
4 ms (turn-on) 4 ms (turn-off)
|
|
maximum current per output common |
7 A
|
|
mechanical durability |
20000000 cycles
|
|
minimum load |
10 mA at 5 V DC for relay output
|
|
local signalling |
1 LED per channel (green)I/O state:
|
|
electrical connection |
11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs and outputs
|
|
maximum cable distance between devices |
Unshielded cable: <30 m for regular input
|
|
insulation |
Between input and internal logic at 500 V AC Non-insulated between inputs Between input groups and output groups at 1500 V AC Between open contact at 750 V AC Between output and internal logic at 500 V AC Non-insulated between outputs
|
|
marking |
CE
|
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
|
|
height |
90 mm
|
|
depth |
84.6 mm
|
|
width |
27.4 mm
|
|
product weight |
0.95 kg
|
|
Environment
standards |
EN/IEC 61131-2 EN/IEC 61010-2-201
|
|
product certifications |
C-Tick CULus
|
|
resistance to electrostatic discharge |
8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2
|
|
resistance to electromagnetic fields |
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
|
|
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
1 kV for I/O conforming to EN/IEC 61000-4-4 2 kV for relay output conforming to EN/IEC 61000-4-4
|
|
surge withstand |
2 kV output common mode conforming to EN/IEC 61000-4-5 1 kV input common mode conforming to EN/IEC 61000-4-5
|
|
resistance to conducted disturbances |
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
|
|
electromagnetic emission |
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
|
|
ambient air temperature for operation |
-10…35 °C vertical installation -10…55 °C horizontal installation
|
|
ambient air temperature for storage |
-25…70 °C
|
|
relative humidity |
10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
|
|
IP degree of protection |
IP20 with protective cover in place
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0…3000 m
|
|
vibration resistance |
3.5 mm at 5…8.4 Hz on DIN rail 3 gn at 8.4…150 Hz on DIN rail 3.5 mm at 5…8.4 Hz on panel 3 gn at 8.4…150 Hz on panel
|
|
shock resistance |
15 gn for 11 ms
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
REACh free of SVHC |
Yes
|
|
EU RoHS Directive |
|
|
Toxic heavy metal free |
Yes
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
|