Product Description
frequency control relay RM35-HZ – range 40..70 Hz
Technical Specifications
Download Product Datasheet
Main
range of product |
Zelio Control
|
|
product or component type |
Modular measurement and control relays
|
|
relay type |
Frequency control relays
|
|
relay name |
RM35HZ21FM
|
|
relay monitored parameters |
Overfrequency and underfrequency 50 or 60 Hz
|
|
time delay type |
Adjustable 0.1...10 s, +/- 10 % on crossing the threshold
|
|
switching capacity in VA |
1250 VA
|
|
minimum switching current |
10 mA 5 V DC
|
|
maximum power consumption in VA |
6 VA AC
|
|
measurement range |
40...70 Hz frequency
|
|
utilisation category |
AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 DC-14 IEC 60947-5-1
|
|
Complementary
reset time |
2000 ms time delay
|
|
maximum switching voltage |
250 V AC/DC
|
|
[Us] rated supply voltage |
120...277 V AC
|
|
[Us] rated supply voltage |
120...277 V AC
|
|
supply voltage limits |
102…308 V AC
|
|
control circuit frequency |
40...70 Hz
|
|
width |
1.38 in (35 mm)
|
|
output contacts |
1 C/O + 1 C/O
|
|
contacts material |
Cadmium free
|
|
nominal output current |
5 A
|
|
maximum input frequency |
70 Hz
|
|
maximum measuring cycle |
200 ms measurement cycle as true rms value
|
|
delay at power up |
0.5 s
|
|
hysteresis |
0.3 % fixed
|
|
measurement accuracy |
+/- 10 % of the full scale value in input +/- 10 % of the full scale value in time delay
|
|
repeat accuracy |
+/- 0.5 % input and measurement circuit +/- 0.5 % time delay
|
|
measurement error |
+/- 0.05 %/°C with temperature variation < +/- 1 % over the whole range with voltage variation
|
|
threshold setting |
-2...10 Hz -10...2 Hz
|
|
marking |
CE : 73/23/EEC CE : EMC 89/336/EEC
|
|
overvoltage category |
III IEC 60664-1
|
|
insulation resistance |
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
|
|
[Ui] rated insulation voltage |
400 V IEC 60664-1
|
|
operating voltage tolerance |
- 15 % + 10 % Un
|
|
supply frequency |
50/60 Hz +/- 10 %
|
|
insulation |
No galvanic insulation between supply and measurement
|
|
operating position |
Any position without
|
|
connections - terminals |
Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
|
|
tightening torque |
5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
|
|
housing material |
Self-extinguishing plastic
|
|
local signalling |
1 LED green power ON 1 LED yellow correct frequency (high R1) 1 LED yellow correct frequency (low R2)
|
|
mounting support |
35 mm symmetrical DIN rail EN/IEC 60715
|
|
electrical durability |
100000 cycles
|
|
mechanical durability |
30000000 cycles
|
|
operating rate |
<= 360 operations/hour full load
|
|
Environment
immunity to microbreaks |
10 ms
|
|
electromagnetic compatibility |
Emission standard for industrial environments EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 Immunity for industrial environments NF EN/IEC 61000-6-2
|
|
standards |
IEC 60255-6 NF EN 60255-6
|
|
product certifications |
GL UL CSA C-Tick GOST
|
|
ambient air temperature for storage |
-40…158 °F (-40…70 °C)
|
|
ambient air temperature for operation |
-4…122 °F (-20…50 °C)
|
|
relative humidity |
95 % 131 °F (55 °C) IEC 60068-2-30
|
|
vibration resistance |
0.35 mm 5…57.6 Hz)IEC 60068-2-6/IEC 60255-21-1 1 gn 57.6…150 Hz)IEC 60068-2-6/IEC 60255-21-1
|
|
shock resistance |
15 gn 11 ms IEC 60255-21-1
|
|
IP degree of protection |
IP20 IEC 60529 terminals) IP30 IEC 60529 casing)
|
|
pollution degree |
3 IEC 60664-1
|
|
dielectric test voltage |
2 kV AC 50 Hz
|
|
non-dissipating shock wave |
4 kV
|
|
Ordering and shipping details
Category |
22380 - RELAYS-MEASUREMENT (RM17-RM35)
|
|
Discount Schedule |
CP2
|
|
GTIN |
00785901564553
|
|
Package weight(Lbs) |
0.12 kg (0.27 lb(US))
|
|
Returnability |
No
|
|
Country of origin |
ID
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
California proposition 65 |
WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
|
|
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
|
|
Contractual warranty
Warranty |
18 months
|
|
More Information
Please visit the product page on our main site for more information.
Learn more