Zelio Timer Relays

RE22R1ACMR

RE22R1ACMR

On and Off-delay Timing Relay – 0.05s…300h – 24…240V AC/DC – 1C/O

Add to Quote
Category:

Product Description

On and Off-delay Timing Relay – 0.05s…300h – 24…240V AC/DC – 1C/O

Technical Specifications

Download Product Datasheet

Main
range of product
Zelio Time
product or component type
Modular timing relay
discrete output type
Relay
device short name
RE22
nominal output current
8 A
Complementary
contacts type and composition
1 C/O timed contact, cadmium free
time delay type
Ac
Act
time delay range
3...30 min
1...10 s
30...300 s
10...100 s
3...30 s
30...300 min
30...300 h
0.3...3 s
0.05...1 s
3...30 h
control type
Rotary knob
Diagnostic button
Potentiometer external
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz
Release input voltage
<= 2.4 V
voltage range
0.85...1.1 Us
supply frequency
50...60 Hz +/- 5 %
connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
tightening torque
0.6…1 N.m conforming to IEC 60947-1
housing material
Self-extinguishing
repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
temperature drift
+/- 0.05 %/°C
voltage drift
+/- 0.2 %/V
setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width
100 ms with load in parallel
30 ms
insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time
120 ms on de-energisation
immunity to microbreaks
10 ms
power consumption in VA
3 VA at 240 V AC
power consumption in W
1.5 W at 240 V DC
switching capacity in VA
2000 VA
minimum switching current
10 mA at 5 V DC
maximum switching current
8 A
maximum switching voltage
250 V AC
electrical durability
100000 cycles, 8 A at 250 V, AC-1
100000 cycles, 2 A at 24 V, DC-1
mechanical durability
10000000 cycles
Rated impulse withstand voltage
5 kV for 1.2…50 µs conforming to IEC 60664-1
Power on delay
100 ms
creepage distance
4 kV/3 conforming to IEC 60664-1
overvoltage category
III conforming to IEC 60664-1
safety reliability data
B10d = 190000
MTTFd = 205.4 years
mounting position
Any position
mounting support
35 mm DIN rail conforming to EN/IEC 60715
status LED
LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
width
22.5 mm
product weight
0.1 kg
Environment
dielectric strength
2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
standards
IEC 61812-1
UL 508
directives
2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
product certifications
CE
CCC
GL
UL
China RoHS
CSA
EAC
RCM
ambient air temperature for operation
-20…60 °C
ambient air temperature for storage
-40…70 °C
IP degree of protection
IP40 housing: conforming to IEC 60529
IP50 front face: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
pollution degree
3 conforming to IEC 60664-1
vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
shock resistance
15 gn not operating for 11 ms conforming to IEC 60068-2-27
5 gn in operation for 11 ms conforming to IEC 60068-2-27
relative humidity
95 % at 25…55 °C
electromagnetic compatibility
Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile

Documents

More Information

Please visit the product page on our main site for more information.


Learn more