Zelio Timer Relays

RE17LCBM

RE17LCBM

off-delay timing relay – control – 1 s..100 h – 24..240 V – solid state output

Add to Quote
Category:

Product Description

off-delay timing relay – control – 1 s..100 h – 24..240 V – solid state output

Technical Specifications

Download Product Datasheet

Main
range of product
Zelio Time
product or component type
Modular timing relay
discrete output type
Solid state
width
17.5 mm
component name
RE17L
time delay type
C
time delay range
10...100 h
6...60 s
6...60 min
1...10 h
1...10 s
1...10 min
0.1...1 s
nominal output current
0.7 A
Complementary
control type
Selector switch front panel
[Us] rated supply voltage
24...240 V AC 50/60 Hz
voltage range
0.85...1.1 Us
supply frequency
50...60 Hz +/- 5 %
release of input voltage
7 V
control signal pulse width
0.05 s typical
insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1
[Uimp] rated impulse withstand voltage
5 kV during 1.2/50 µs
power on delay
100 ms
connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
tightening torque
0.6…1 N.m conforming to IEC 60947-1
dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
housing material
Self-extinguishing
repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
temperature drift
+/- 0.05 %/°C
voltage drift
+/- 0.2 %/V
setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
reset time
350 ms on de-energisation typical
on-load factor
100 %
power consumption in VA
0…3 VA at 240 V AC
maximum power consumption in W
1.5 W at 240 V DC
breaking capacity
0.5 A AC/DC conforming to UL
0.7 A AC/DC at 20 °C
operating frequency
10 Hz
maximum output current
20 A <= 10 ms
minimum switching current
10 mA
maximum leakage current
5 mA
maximum switching voltage
250 V AC
maximum voltage drop
<4 V 3-wire
<8 V 2-wire
electrical durability
100000000 cycles
marking
CE
creepage distance
4 kV/3 conforming to IEC 60664-1
safety reliability data
MTTFd = 353.8 years
B10d = 320000
mounting position
Any position in relation to normal vertical mounting plane
mounting support
35 mm DIN rail conforming to EN/IEC 60715
product weight
0.068 kg
time delay type
C
functionality
Off-delay timing
compatibility code
RE17
Environment
immunity to microbreaks
20 ms
derating factor
5 mA/°C
standards
2004/108/EC
EN 61000-6-3
2006/95/EC
EN 61000-6-2
IEC 61812-1
EN 61000-6-4
EN 61000-6-1
product certifications
CSA
GL
CULus
ambient air temperature for storage
-30…60 °C
ambient air temperature for operation
-20…60 °C
IP degree of protection
IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
relative humidity
93 % without condensation conforming to IEC 60068-2-30
electromagnetic compatibility
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
Conducted and radiated emissions: , class B, conforming to EN 55022
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile