Empty enclosure

D150-CI43

Eaton xEnergy Safety Ci empty enclosure cover

Add to Quote
Category:

Product Description

Cap, transparent smoky gray, HxWxD=250x375x50mm

EL Number (Norway)

2502194

Cover transparent smoky, degree of protection IP65, patented cover fasteners with integrated overpressure compensation, sealable cover fasteners, continuous foamed gasket, mounting depth with mounting plate=150mm, can be used for CI bases E, X and V, lock mechanism type: actuation with tools (not accessible to unqualified personnel)

Technical Specifications

General specifications
Product name
Eaton xEnergy Safety Ci empty enclosure cover
Part no.
D150-CI43
EAN
4015080385608
Product Length/Depth
90 millimetre
Product height
250 millimetre
Product width
375 millimetre
Product weight
1.391 kilogram
Compliances
RoHS conform
Product Tradename
xEnergy Safety Ci
Product Type
Empty enclosure
Product Sub Type
Cover
Globally Marketable
Yes
Delivery program
Type
Basic enclosure
Enclosure cover
xEnergy Safety Ci
Accessory/spare part type
Enclosure cover without apertures
Color
Transparent, smoky gray
Other
Technical Data - Mechanical
Unit type
Modular system
Surface finishing
Untreated
Mounting depth
150 mm
Material
Plastic
Cover/door type
Transparent
Suitable for enclosure building length/depth
0 mm
Suitable for enclosure building width
0 mm
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
13 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
26 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
14 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
13 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
28 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
27 W
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65, with base unit
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Additional information
Functions
Basic enclosure
RAL-number
0
Special features
Sealable cover fasteners
Suitable for
Outdoor set-up
Used with
U-CI43…
xEnergy Safety Ci
Basic enclosure
Enclosure cover

Documents

More Information

Please visit the product page on our main site for more information.


Learn more