Insulated enclosure, IP65_x, +emergency switching off mushroom push-button, for PKZ01

EL Number (Norway)

4365003

Insulated enclosure for PKZM01, degree of protection IP65 integrated terminal for PE(N) connection., With emergency switching off mushroom-headed pushbutton, maintained, top and bottom 2 M25 knockout cable entries each

Technical Specifications

General specifications
Product name
Eaton Moeller® series CI Insulated enclosure
Part no.
CI-PKZ01-PVT
EAN
4015082814069
Product Length/Depth
177 millimetre
Product height
158 millimetre
Product width
80 millimetre
Product weight
0.3 kilogram
Compliances
CE
Product Tradename
CI
Product Type
Insulated enclosure
Product Sub Type
None
Globally Marketable
Yes
Features & Functions
Enclosure material
Plastic
Fitted with:
PE(N) terminal
Emergency switching off mushroom push-button
Functions
Maintained
Knockouts
2 x M25 (cable entry knockout with thread at the bottom)
2 x M25 (cable entry knockout with thread at the top)
2 x M20 (cable entry knockouts at the rear)
Hard mirror with cable entry knockouts (can be cut out)
General information
Degree of protection
IP65
NEMA Other
Model
Surface mounting
Product category
Accessories
Suitable for
Emergency stop
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
10 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.