Three-phase busbar link, Circuit-breaker: 2, 90 mm, For PKZM0-… or PKE12, PKE32 without side mounted auxiliary contacts or voltage releases

EL Number (Norway)

4357208

Three-phase busbar link 3 poles for feeder unit of 2 PKZM0-… without auxiliary contact or voltage release built on laterally, can be extended by rotating installation, length 90mm protective against direct contact., Ue = 690 V, Iu = 63 A

Technical Specifications

General specifications
Product name
Eaton Moeller® series B3 Accessory Three-phase busbar link
Part no.
B3.0/2-PKZ0
EAN
4015080639619
Product Length/Depth
90 millimetre
Product height
34 millimetre
Product width
11 millimetre
Product weight
0.035 kilogram
Certifications
CSA Class No.: 3211-06
CSA
IEC/EN 60947-4-1
UL 508
CSA-C22.2 No. 14
CSA File No.: 98494
UL
CE
UL File No.: E36332
UL Category Control No.: NLRV
Product Tradename
B3
Product Type
Accessory
Product Sub Type
Three-phase busbar link
Globally Marketable
Yes
Features & Functions
Color
Black
Electric connection type
Fork
Features
Insulated
Functions
Can be extended by rotating installation
Number of phases
3
Number of poles
Three-pole
General information
Mounting width
45 mm
Overvoltage category
III
Pollution degree
3
Product category
Accessories
Rated impulse withstand voltage (Uimp)
6000 V AC
Suitable for
2 Circuit-breakers
Used with
PKZ0
PKE12
PKE32
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Electrical rating
Rated operational voltage (Ue) - max
690 V
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
63 A
Short-circuit rating
Rated conditional short-circuit current (Iq)
0 kA
Rated short-time withstand current (Icw)
0 kA
Design verification
Equipment heat dissipation, current-dependent Pvid
3 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.