Product Description
TeSys SK control relay – 2 NO – <= 690 V - 110 V AC coil
Technical Specifications
Download Product Datasheet
Main
range |
TeSys
|
|
product name |
TeSys CASK
|
|
product or component type |
Control relay
|
|
device short name |
CA2SK
|
|
contactor application |
Control circuit
|
|
utilisation category |
AC-15 DC-13
|
|
pole contact composition |
2 NO
|
|
[Ue] rated operational voltage |
<= 690 V <= 400 Hz
|
|
control circuit type |
AC at 50/60 Hz
|
|
[Uc] control circuit voltage |
110 V AC 50/60 Hz
|
|
Complementary
[Ith] conventional free air thermal current |
10 A (at 55 °C)
|
|
associated fuse rating |
10 A gL conforming to VDE 0660 10 A gL conforming to IEC 60947
|
|
[Ui] rated insulation voltage |
690 V conforming to IEC 60947 690 V conforming to VDE 0110 group C 690 V conforming to BS 5424 690 V conforming to UL 508 690 V conforming to CSA C22.2 No 14
|
|
mounting support |
Rail Plate
|
|
connections - terminals |
Screw clamp terminals 1 cable(s) 1.5…6 mm²solid Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.5…6 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.35…6 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.35…1.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.35…2.5 mm²flexible without cable end
|
|
tightening torque |
0.8 N.m - on screw clamp terminals pozidriv No 1 screw head
|
|
control circuit voltage limits |
Drop-out: 0.2...0.75 Uc (at <50 °C) Operational: 0.85...1.1 Uc (at <50 °C)
|
|
operating time |
6...8 ms coil de-energisation and NO opening 7...14 ms coil energisation and NO closing
|
|
mechanical durability |
10 Mcycles
|
|
maximum operating rate |
1200 cyc/h
|
|
inrush power in VA |
16 VA (at 20 °C)
|
|
hold-in power consumption in VA |
4.2 VA (at 20 °C)
|
|
heat dissipation |
1.4 W
|
|
height |
56 mm
|
|
width |
27 mm
|
|
depth |
55.5 mm
|
|
product weight |
0.132 kg
|
|
Environment
standards |
VDE 0660 NF C 63-110 BS 5424 IEC 60947
|
|
product certifications |
CULus
|
|
IP degree of protection |
IP2x
|
|
protective treatment |
TC conforming to IEC 60068
|
|
ambient air temperature for operation |
-20…50 °C
|
|
ambient air temperature for storage |
-50…70 °C
|
|
operating altitude |
2000 m without
|
|
Offer Sustainability
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
|
Contractual warranty
Warranty |
18 months
|
|
More Information
Please visit the product page on our main site for more information.
Learn more