Product Description
variable speed drive – 45kW- 400V – 3 phases – ATV340 Ethernet
variable speed drive – 45kW- 400V – 3 phases – ATV340 Ethernet
variable speed drive – 45kW- 400V – 3 phases – ATV340 Ethernet
Download Product Datasheet
Characteristics
range of product
product or component type
device application
device short name
variant
product destination
Synchronous motors
mounting mode
EMC filter
IP degree of protection
IP20 conforming to IEC 60529
degree of protection
type of cooling
supply frequency
network number of phases
[Us] rated supply voltage
motor power kW
45 kW for heavy duty
motor power hp
60 hp for heavy duty
line current
84.2 A at 480 V with internal line choke (normal duty)
81.4 A at 380 V with internal line choke (heavy duty)
71.8 A at 480 V with internal line choke (heavy duty)
81.4 A
71.8 A
prospective line Isc
apparent power
59.7 kVA at 480 V (heavy duty)
continuous output current
88 A at 4 kHz for heavy duty
maximum transient current
132 A during 60 s (heavy duty)
127.2 A during 2 s (normal duty)
132 A during 2 s (heavy duty)
asynchronous motor control profile
Optimized torque mode
Variable torque standard
synchronous motor control profile
Permanent magnet motor
speed drive output frequency
nominal switching frequency
switching frequency
2.5...8 kHz with derating factor
safety function
number of preset speeds
communication port protocol
Modbus serial
Ethernet/IP
option card
Slot GP-X: output relay extension module
Slot GP-ENC: 5/12 V digital encoder interface module
Slot GP-ENC: analog encoder interface module
Slot GP-ENC: resolver encoder interface module
output voltage
permissible temporary current boost
1.2 x In during 60 s (normal duty)
motor slip compensation
Can be suppressed
Adjustable
Automatic whatever the load
acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
braking to standstill
protection type
Safe torque off: motor
Motor phase loss: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent: drive
Output overcurrent between motor phase and earth: drive
Output overcurrent between motor phases: drive
Short-circuit between motor phase and earth: drive
Short-circuit between motor phases: drive
Motor phase loss: drive
DC Bus overvoltage: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Input supply loss: drive
Exceeding limit speed: drive
Break on the control circuit: drive
frequency resolution
Analog input: 0.012/50 Hz
electrical connection
Line side: screw terminal70...120 mm²/AWG 1/0...250 kcmil
DC bus: screw terminal70...120 mm²/AWG 1/0...250 kcmil
Motor: screw terminal70...120 mm²/AWG 1/0...250 kcmil
connector type
connector(s)1 x RJ45, Modbus serial for HMI on front face
connector(s)2 x RJ45, Ethernet IP/Modbus TCP on front face
physical interface
transmission frame
transmission rate
10/100 Mbit/s for Ethernet IP/Modbus TCP
exchange mode
data format
type of polarization
number of addresses
method of access
Slave Modbus TCP
supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
local signalling
Embedded communication status: 5 LED (dual colour)
Communication module status: 2 LED (dual colour)
Presence of voltage: 1 LED (red)
width
height
depth
product weight
analogue input number
analogue input type
AI1, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI1, AI3 software-configurable temperature probe or water level sensor
discrete input number
discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
DI1...DI8 programmable, 24 V DC (<= 30 V), impedance: 4.4 kOhm
input compatibility
DI1...DI8: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI7, DI8: pulse input level 1 PLC conforming to IEC 65A-68
discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI7, DI8), < 0.6 V (state 0), > 2.5 V (state 1)
analogue output number
analogue output type
Software-configurable current AQ1, AQ2: 0...20 mA impedance 500 Ohm, resolution 10 bits
discrete output number
input/output type
Logic output DQ+: 0…1 kHz, <= 30 V DC, 100 mA
Programmable as pulse output DQ+: 0…30 kHz, <= 30 V DC, 20 mA
sampling duration
5 ms +/- 1 ms (DI7, DI8) - pulse input
1 ms +/- 1 ms (AI1, AI2, AI3) - analog input
5 ms +/- 1 ms (AQ1, AQ2) - analog output
accuracy
+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
linearity error
AQ1, AQ2: +/- 0.2 % for analog output
relay output number
relay output type
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time
minimum switching current
maximum switching current
Relay output R1 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 30 V DC
Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation
insulation resistance
noise level
power dissipation in W
Forced convection: 943 W at 380 V, switching frequency 4 kHz (heavy duty)
Natural convection: 115 W at 380 V, switching frequency 4 kHz (normal duty)
Forced convection: 917 W at 380 V, switching frequency 4 kHz (normal duty)
volume of cooling air
operating position
electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree
vibration resistance
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance
relative humidity
ambient air temperature for operation
40…60 °C with current derating (normal duty)
-15…50 °C without current derating (heavy duty)
-15…40 °C without current derating (normal duty)
ambient air temperature for storage
operating altitude
1000...4800 m with current derating 1 % per 100 m
environmental characteristic
Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
standards
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
product certifications
UL
REACH
CSA
marking
Sustainable offer status
REACh Regulation
EU RoHS Directive
EU RoHS Declaration
Mercury free
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE