Molded Case Circuit Breaker

422567

無熔絲開關 3P1600A

Add to Quote

Product Description

Technical Specifications

Rated permanent current Iu 1600 A
Rated voltage 220-690 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz 70 kA
Overload release current setting 640-1600 A
Adjustment range short-term delayed short-circuit release 960-16000 A
Adjustment range undelayed short-circuit release 20000-20000 A
Device construction Built-in device fixed built-in technique
Integrated earth fault protection No
Type of electrical connection of main circuit Screw connection
Suitable for DIN rail (top hat rail) mounting No
DIN rail (top hat rail) mounting optional No
Number of auxiliary contacts as change-over contact 3
With switched-off indicator Yes
With integrated under voltage release Yes
Number of poles 3
Position of connection for main current circuit Front side
Type of control element Toggle
Complete device with protection unit Yes
Motor drive integrated No
Motor drive optional Yes
Degree of protection (IP) IP30

Documents

Instruction Use
LE07037AB.pdf pdf ( 0.94 Mo)
Instruction Use
LE08011AA.pdf pdf ( 0.44 Mo)
Technical Sheet
Technical Sheet
F01964EN01.pdf pdf ( 1.05 Mo)
Technical Guide
3D Autocad
422567.dwg dwg ( 0.13 Mo)
3D Autocad
422315.dwg dwg ( 0.18 Mo)

More Information

Please visit the product page on our main site for more information.