Electronic pressure sensors, Pressure sensors XM, transmitter, XMLP, 40 bar, 7/16 female, 4…20 mA, M12, set of 1
Electronic pressure sensors, Pressure sensors XM, transmitter, XMLP, 40 bar, 7/16 female, 4…20 mA, M12, set of 1
Main | |
---|---|
Range of product | Telemecanique Pressure sensors XM |
Product or component type | Electronic pressure sensors |
Pressure sensor type | Pressure transmitter |
Pressure sensor name | XMLP |
Electrical circuit type | Control circuit |
Pressure sensor size | 40 bar |
Local display | Without |
Controlled fluid |
Fresh water (0…135 °C)
Air (-40…135 °C) Hydraulic oil (-40…135 °C) Gas (-40…135 °C) Refrigeration fluid (-40…135 °C) |
Fluid connection type | SAE 7/16-20UNF-2B (female) with schrader |
Electrical connection | 1 male connector M12 4 pins |
[Us] rated supply voltage | 12...24 V DC SELV (voltage limits: 7…33 V) |
Current consumption | < 23 mA |
Type of output signal | Analogue |
Analogue output function | 4...20 mA, 2-wire |
Quantity per set | Set of 1 |
Type of packing | Individual |
Complementary | |
Pressure setting range | 0…40 bar |
Maximum permissible accidental pressure | 120 bar |
Destruction pressure | 240 bar |
Materials in contact with fluid | Stainless steel type AISI 303 |
Operating position | Any position |
Protection type |
Load short-circuit
Reverse polarity |
Electromagnetic compatibility |
Electrostatic discharge immunity test conforming to EN/IEC 61000-4-2 8 kV air, 4 kV contact
1.2/50 µs shock waves immunity test conforming to EN/IEC 61000-4-5 1 kV 42 Ohm Immunity to magnetic fields conforming to EN/IEC 61000-4-8 100 A/m 50 Hz Electrical fast transient/burst immunity test conforming to EN/IEC 61000-4-4 4 kV Susceptibility to electromagnetic fields conforming to EN/IEC 61000-4-3 10 V/m 80...3000 MHz Radiated RF fields conforming to EN/IEC 61000-4-6 10 V 0.01...80 MHz |
[Uimp] rated impulse withstand voltage | 0.5 kV |
Response time on output | <= 2 ms 10...90 % of full scale |
Measurement accuracy | +/- 0.5 % of the measuring range |
Accuracy | 0.1 % of the measuring range |
Drift of the sensitivity | +/- 0.02 % of measuring range/°K |
Drift of the zero point | +/- 0.02 % of measuring range/°K |
Mechanical durability | 10000000 cycles |
Net weight | 0.1 kg |
Diameter | 26 mm |
Length | 44 mm |
Environment | |
Standards |
NSF ANSI 61
EN/IEC 61326-2-3 |
Product certifications |
CE
cULus RCM EAC |
Protective treatment | TC |
Ambient air temperature for operation | -30…85 °C |
Ambient air temperature for storage | -50…100 °C |
Vibration resistance | 20 gn (f = 15…2000 Hz) conforming to EN/IEC 60068-2-6 |
Shock resistance | 100 gn for 11 ms conforming to EN/IEC 60068-2-27 |
IP degree of protection |
IP65 conforming to EN/IEC 60529
IP67 conforming to EN/IEC 60529 IP69K conforming to EN/IEC 60529 |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 4.000 cm |
Package 1 Width | 4.400 cm |
Package 1 Length | 8.000 cm |
Package 1 Weight | 100.000 g |
Unit Type of Package 2 | S01 |
Number of Units in Package 2 | 24 |
Package 2 Height | 15.000 cm |
Package 2 Width | 15.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 2.704 kg |
Offer Sustainability | |
Sustainable offer status | Green Premium product |
REACh Regulation | REACh Declaration |
EU RoHS Directive | EU RoHS Declaration |
Mercury free | Yes |
RoHS exemption information | Yes |
Environmental Disclosure | Product Environmental Profile |
California proposition 65 | WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |