ATV 配件

VW3A4705

VW3A4705

EMC radio interference input filter – for variable speed drive – 70 A

Add to Quote
Category:

Product Description

EMC radio interference input filter – for variable speed drive – 70 A

Technical Specifications

Download Product Datasheet

Main
range of product
Altivar
product or component type
EMC input filter
range compatibility
Altivar Process ATV900
Altivar Process ATV600
product compatibility
Variable speed drive ATV630 wall mount, motor: 30 kW, 380...480 V
Variable speed drive ATV630 wall mount, motor: 15 kW, 200...240 V
Variable speed drive ATV650 wall mount, motor: 30 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 30 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 15 kW, 200...240 V
Variable speed drive ATV950 wall mount, motor: 30 kW, 380...480 V
product specific application
Radio interference input filter
[In] rated current
70 A
thermal losses
10 W
network number of phases
Three phase
Complementary
electrical connection
Terminal 50 mm² AWG 1/0
maximum motor cable length
150 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C2, 380...480 V
300 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C3, 380...480 V
150 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C2, 200...240 V
300 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C3, 200...240 V
50 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C1, 200...240 V
50 m shielded motor cable 4 kHz conforming to EN/IEC 61800-3 category C1, 380...480 V
maximum earth leakage current
13.9 mA at 400 V 50 Hz TN
13.9 mA at 400 V 50 Hz TT
power supply voltage
200…240 V
380…480 V
tolerance
10 %
mechanical robustness
Shocks class 3M4 conforming to IEC 60721-3-3
Vibrations class 3M4 conforming to IEC 60721-3-3
width
100 mm
height
328 mm
depth
175 mm
product weight
6.1 kg
Environment
IP degree of protection
IP20mounting side by side
IP21with kit VW3A47905
relative humidity
5…95 % without condensation conforming to IEC 61800-5-1
ambient air temperature for operation
-10…50 °C (without current derating)
50…60 °C (with current derating 1.5 % per °C)
ambient air temperature for storage
-40…70 °C
operating altitude
0...1000 m without current derating
1000...4000 m with current derating 1 % per 100 m
standards
EN/IEC 61800-3
Offer Sustainability
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation

Documents

More Information

Please visit the product page on our main site for more information.