産品概述
controller M241 24 IO relay Ethernet CAN master
技術規格
Download Product Datasheet
Main
range of product |
Modicon M241
|
|
product or component type |
Logic controller
|
|
[Us] rated supply voltage |
100...240 V AC
|
|
discrete input number |
14, discrete input 8 fast input conforming to IEC 61131-2 Type 1
|
|
discrete output type |
Transistor Relay
|
|
discrete output number |
6 relay 4 transistor 4 fast output
|
|
discrete output voltage |
5...125 V DC for relay output 5...250 V AC for relay output 24 V DC for transistor output
|
|
discrete output current |
2 A for relay output (Q4...Q9) 0.1 A for fast output (PTO mode) (TR0...TR3) 0.5 A for transistor output (TR0...TR3)
|
|
Complementary
discrete I/O number |
24
|
|
maximum number of I/O expansion module |
7 (local) 14 (remote)
|
|
supply voltage limits |
85…264 V
|
|
network frequency |
50/60 Hz
|
|
discrete input logic |
Sink or source
|
|
discrete input voltage |
24 V
|
|
discrete input voltage type |
DC
|
|
voltage state 1 guaranteed |
>= 15 V for input
|
|
voltage state 0 guaranteed |
<= 5 V for input
|
|
discrete input current |
5 mA for input
|
|
input impedance |
4.7 kOhm for input
|
|
response time |
50 µs turn-on, I0...I13 terminal(s) for input
|
|
configurable filtering time |
1 µs for fast input
|
|
discrete output logic |
Positive logic (source)
|
|
output voltage limits |
125 V DC relay output 30 V DC transistor output 277 V AC relay output
|
|
maximum output frequency |
1 kHz for transistor output 20 kHz for fast output (PWM mode) 100 kHz for fast output (PLS mode)
|
|
accuracy |
+/- 0.1 % at 0.02…0.1 kHz for fast output +/- 1 % at 0.1…1 kHz for fast output
|
|
protection type |
Short-circuit protection for transistor output Short-circuit and overload protection with automatic reset for transistor output Reverse polarity protection for transistor output Without protection for relay output
|
|
reset time |
10 ms automatic reset output 12 s automatic reset fast output
|
|
memory capacity |
8 MB for program 64 MB for system memory RAM
|
|
data backed up |
128 MB built-in flash memory for backup of user programs
|
|
data storage equipment |
<= 16 GB SD card (optional)
|
|
battery type |
BR2032 lithium non-rechargeable, battery life: 4 year(s)
|
|
backup time |
2 years at 25 °C
|
|
execution time for 1 KInstruction |
0.3 ms for event and periodic task 0.7 ms for other instruction
|
|
application structure |
4 cyclic master tasks 8 external event tasks 8 event tasks 3 cyclic master tasks + 1 freewheeling task
|
|
realtime clock |
With
|
|
clock drift |
<= 60 s/month at 25 °C
|
|
positioning functions |
PTO function 4 channel(s) (positioning frequency: 100 kHz)
|
|
counting input number |
4 fast input (HSC mode) at 200 kHz 14 standard input at 1 kHz
|
|
control signal type |
A/B at 100 kHz for fast input (HSC mode) Pulse/direction at 200 kHz for fast input (HSC mode) Single phase at 200 kHz for fast input (HSC mode)
|
|
integrated connection type |
Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface USB port with mini B USB 2.0 connector Ethernet with RJ45 connector CANopen J1939 with male SUB-D 9 connector
|
|
supply |
(serial 1)serial link supply: 5 V, <200 mA
|
|
transmission rate |
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for bus length of 3 m for USB 10/100 Mbit/s for Ethernet 1000 kbit/s for bus length of 20 m for CANopen 800 kbit/s for bus length of 40 m for CANopen 500 kbit/s for bus length of 100 m for CANopen 250 kbit/s for bus length of 250 m for CANopen 125 kbit/s for bus length of 500 m for CANopen 50 kbit/s for bus length of 1000 m for CANopen 20 kbit/s for bus length of 2500 m for CANopen
|
|
communication port protocol |
Non isolated serial link: Modbus master/slave
|
|
port Ethernet |
10BASE-T/100BASE-TX - 1 port(s) copper cable
|
|
ethernet services |
SNMP client/server Modbus TCP slave device Modbus TCP server Modbus TCP client IEC VAR ACCESS FTP client/server SQL client DHCP client Ethernet/IP adapter Send and receive email from the controller based on TCP/UDP library Web server (WebVisu & XWeb system) OPC UA server DNS client
|
|
local signalling |
1 LED (green)PWR: 1 LED (green)RUN: 1 LED (red)module error (ERR): 1 LED (red)I/O error (I/O): 1 LED (green)SD card access (SD): 1 LED (red)BAT: 1 LED (green)SL1: 1 LED (green)SL2: 1 LED (red)bus fault on TM4 (TM4): 1 LED per channel (green)I/O state: 1 LED (green)Ethernet port activity: 1 LED (green)CANopen run: 1 LED (green)CANopen error:
|
|
electrical connection |
removable screw terminal blockfor inputs and outputs (pitch 5.08 mm) removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm)
|
|
maximum cable distance between devices |
Unshielded cable: <50 m for input Shielded cable: <10 m for fast input Unshielded cable: <50 m for output Shielded cable: <3 m for fast output
|
|
insulation |
Between supply and internal logic at 500 V AC Non-insulated between supply and ground
|
|
marking |
CE
|
|
sensor power supply |
24 V DC at 400 mA supplied by the controller
|
|
surge withstand |
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 1 kV input common mode conforming to EN/IEC 61000-4-5 1 kV transistor output common mode conforming to EN/IEC 61000-4-5
|
|
web services |
Web server
|
|
maximum number of connections |
16 Ethernet/IP device 8 Modbus server
|
|
CANopen feature profile |
DR 303-1 DS 301 V4.02
|
|
number of slave |
63 CANopen:
|
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
|
|
height |
90 mm
|
|
depth |
95 mm
|
|
width |
150 mm
|
|
product weight |
0.53 kg
|
|
Environment
standards |
ANSI/ISA 12-12-01 CSA C22.2 No 142 CSA C22.2 No 213 EN/IEC 61131-2:2007 Marine specification (LR, ABS, DNV, GL) UL 1604 UL 508
|
|
product certifications |
CSA IACS E10 RCM CULus
|
|
resistance to electrostatic discharge |
8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2
|
|
resistance to electromagnetic fields |
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
|
|
resistance to fast transients |
2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 1 kV (input) conforming to EN/IEC 61000-4-4 1 kV (transistor output) conforming to EN/IEC 61000-4-4
|
|
resistance to conducted disturbances |
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
|
|
electromagnetic emission |
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines) at 0.5…300 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
|
|
immunity to microbreaks |
10 ms
|
|
ambient air temperature for operation |
-10…50 °C (vertical installation) -10…55 °C (horizontal installation)
|
|
ambient air temperature for storage |
-25…70 °C
|
|
relative humidity |
10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
|
|
IP degree of protection |
IP20 with protective cover in place
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0…3000 m
|
|
vibration resistance |
3.5 mm at 5…8.4 Hz on symmetrical rail 3 gn at 8.4…150 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 3 gn at 8.4…150 Hz on panel mounting
|
|
shock resistance |
15 gn for 11 ms
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
|
PVC free |
Yes
|
|