Zelio Timer Relays

RE17RCMU

RE17RCMU

off-delay timing relay – 1 s..100 h – 24..240 V AC – 1 OC

加入詢價單

産品概述

off-delay timing relay – 1 s..100 h – 24..240 V AC – 1 OC

技術規格

Download Product Datasheet

Main
range of product
Zelio Time
product or component type
Modular timing relay
discrete output type
Relay
width
17.5 mm
device short name
RE17R
time delay type
C
time delay range
6...60 s
1...10 h
1...10 min
6...60 min
0.1...1 s
1...10 s
10...100 h
nominal output current
8 A
Complementary
contacts type and composition
1 C/O
contacts material
Cadmium free
height
90 mm
depth
72 mm
control type
Selector switch front panel
[Us] rated supply voltage
24...240 V AC 50/60 Hz
24 V DC
voltage range
0.85...1.1 Us
supply frequency
50...60 Hz +/- 5 %
release of input voltage
10 V
connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
tightening torque
0.6…1 N.m conforming to IEC 60947-1
housing material
Self-extinguishing
repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
temperature drift
+/- 0.05 %/°C
voltage drift
+/- 0.2 %/V
setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
control signal pulse width
100 ms with load in parallel typical
30 ms typical
insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1
reset time
120 ms on de-energisation typical
on-load factor
100 %
power consumption in VA
0…32 VA at 240 V AC
maximum power consumption in W
0.6 W at 24 V DC
minimum switching current
10 mA at 5 V DC
maximum switching current
8 A AC/DC
maximum switching voltage
250 V AC
breaking capacity
2000 VA
operating frequency
10 Hz
electrical durability
100000 cycles (8 A at 250 V AC maximum) for resistive load
mechanical durability
10000000 cycles
dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
[Uimp] rated impulse withstand voltage
5 kV during 1.2/50 µs
power on delay
100 ms
marking
CE
creepage distance
4 kV/3 conforming to IEC 60664-1
safety reliability data
B10d = 270000
MTTFd = 296.8 years
mounting position
Any position in relation to normal vertical mounting plane
mounting support
35 mm DIN rail conforming to EN/IEC 60715
local signalling
LED indicator for on steady: relay energised, no timing in progress
LED indicator for flashing: timing in progress 80 % ON and 20 % OFF
LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF
product weight
0.07 kg
time delay type
C
functionality
Off-delay timing
compatibility code
RE17
Environment
immunity to microbreaks
20 ms
standards
EN 61000-6-4
EN 61000-6-2
EN 61000-6-3
2004/108/EC
2006/95/EC
IEC 61812-1
EN 61000-6-1
product certifications
CULus
GL
CSA
ambient air temperature for storage
-30…60 °C
ambient air temperature for operation
-20…60 °C
IP degree of protection
IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
relative humidity
93 % without condensation conforming to IEC 60068-2-30
electromagnetic compatibility
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
Conducted and radiated emissions: , class B, conforming to EN 55022
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile

文檔

更多資料

請訪問我們主站的產品頁面了解更多信息。


進一步了解