NH fuse-switch 3p flange connection M10 max. 150 mm²; mounting plate; NH1

EL Number (Norway)

1624018

NH fuse switch-disconnector 3 pole with M10 flat terminal max. 150 mm²; mounting plate; for NH1 fuse-links; optionally lockable with XNH-XLOCK and padlock

技術規格

General specifications
Product name
Eaton xEffect XNH device for mounting plate
Part no.
XNH1-A250
EAN
4015081779703
Product Length/Depth
306 millimetre
Product height
117 millimetre
Product width
184 millimetre
Product weight
1.991 kilogram
Compliances
RoHS conform
Certifications
IEC/EN 60947-3
Product Tradename
xEffect
Product Type
XNH device for mounting plate
Product Sub Type
None
Globally Marketable
Yes
Delivery program
Type
Basic device
Color
Gray
Number of poles
Three-pole
Actuator type
Cover grip
Technical Data - Electrical
Voltage test
Yes, sliding inspection windows
Voltage rating at AC
400 V (AC-23B)
500 V (AC-22B)
690 V (AC-21B)
Voltage rating at DC
250 V (DC-22B)
440 V (DC-21B)
Rated operating voltage (Ue) at AC - max
690 V
Rated insulation voltage (Ui)
800
Rated impulse withstand voltage (Uimp)
8 kV
Rated uninterrupted current (Iu)
250 A
Rated conditional short-circuit current (Iq)
120 kA
Rated operation current (Ie)
250 A
Rated operational current
250 A (AC-22B)
250 A (AC-21B)
250 A (DC-21B)
250 A (AC-23B)
250 A (DC-22B)
Rated short-time withstand current (Icw)
6 kA
Rated conditional short-circuit rating
100 kA (690 V)
120 kA (500 V)
Conditioned rated short-circuit current Iq
120 kA
Frequency rating
40 Hz - 60 Hz
Frequency rating of contacts
40 Hz - 60 Hz
Creepage resistance
CTI 600
Power rating at AC-23, 400 V
0 kW
Rated operation power at AC-23, 400 V
0 kW
Permitted power loss per fuse link - max
23 W
Electrical connection type of main circuit
Screw connection
Operating altitude without derating - max
2000 mm
Overvoltage category
III
Pollution degree
3
Direction of incoming supply
As required
Lifespan, electrical
200 operations
Technical Data - Mechanical
Activation type
Dependent manual activation
Actuator position
Front side
Size
NH1 fuse
Mounting method
DIN rail
Mounting plate
Mounting position
Vertical or horizontal
Material
Polyamide
Degree of protection
IP10 (handle cover open, XNH installed)
IP2XC (contact protection, XNH installed)
IP20 (operating status, XNH installed)
Degree of protection (front side)
Other
Connection type
Flat connection
Terminal capacity (copper band)
6 mm x 16 mm x 0.8 mm (6x) at box terminal
Terminal capacity (copper busbar)
Bolt diameter at flange connection: M10
Max. 37 mm cable lug width at flange connection
30 mm x 10 mm
Terminal capacity (copper strip)
16 mm x 0.8 mm (10x) at box terminal
Terminal capacity (stranded cable)
70 mm² - 95 mm² (2x) at double clamp-type terminal
35 mm² - 150 mm² at box terminal
10 mm² -150 mm² at clamp-type terminal
25 mm² - 150 mm² at box terminal
Cable entry type
Other
Locking facility
Yes, optional
Suitable for fuses
NH1
Lifespan, mechanical
1400 operations
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
250 A
Equipment heat dissipation, current-dependent
16 W
Heat dissipation per pole, current-dependent
5.3 W
Heat dissipation at 80% without fuses
10.2 W
Ambient operating temperature details
Ambient temperature range: -25 °C - 55 °C
Heat deflection temperature
125 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 800 V AC
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Features
Halogen free
Standard sealable
Flammability characteristics (UL)
Self-extinguishing (UL 94)
Special features
Current paths of electrolytic copper, silver-plated
Permanent operation (rated operating mode)
Suitable for
Ground mounting

文檔