Busbar system component

NZM2-XAD250

Eaton xEffect SASY 60i MCCB adapter

加入詢價單

産品概述

Busbar adapter, 3p, for NZM2, 250A, UL508

EL Number (Norway)

2465044

Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30×5-10, double t and triple t profile, rated operational current Ie=250A, can be used for NZM2, PN2, N(S)2, adapter width=106mm, rated operating voltage Ue=690VAC, threaded connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved

技術規格

General specifications
Product name
Eaton xEffect SASY 60i MCCB adapter
Part no.
NZM2-XAD250
EAN
4015081043736
Product Length/Depth
192 millimetre
Product height
35 millimetre
Product width
106 millimetre
Product weight
0.828 kilogram
Compliances
CE marking
UL CSA09 (refer to approbation report)
UL508A
CSA-C22.2 No. 14
IEC 60439-1
RoHS conform
Certifications
CSA (Class No. 3211-37)
CSA (File No. 236217)
UL (File No. E300273)
UL (Category Control Number NMTR, NMTR7)
North America (UL listed, CSA certified)
Product Tradename
xEffect SASY 60i
Product Type
Busbar system component
Product Sub Type
MCCB adapter
Globally Marketable
Yes
Delivery program
Type
60 mm system
Busbar adapters for NZM
Compact system
Nominal current
250 A
Number of poles
Three-pole
Technical Data - Electrical
Voltage rating (UL CSA 13)
Max. 600 V AC
Voltage rating at AC
690 V AC
Rated operation current (Ie)
250 A
Electric connection type
Other
Creepage resistance
CTI 200
Technical Data - Mechanical
Rail width
30 mm
Degree of protection
Feeder circuits
Busbar distance
60 mm
Busbar thickness - min
5 mm
Busbar thickness - max
10 mm
Busbar adapter width
106 mm
Adapter width
106 mm
Design verification as per IEC/EN 61439 - technical data
Temperature resistance
Up to 120 °C
Additional information
Features
Self-extinguishing acc. UL 94
Functions
Busbar adapters for NZM
Current limiting circuit breaker, refer to approbation report
Component adapter for circuit breakers and switch-disconnector
Suitable for
Surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Used with
N(S)2
PN2,
Feeder circuits
NZM2
Busbar adapters for NZM
Compact system
60 mm system