Actuator

LS-XWA-ZBZ

Eaton Moeller® series LS Actuator

加入詢價單
分類:

産品概述

Actuator, angled, long

EL Number (Norway)

4356184

Actuator, Basic function: actuators, Part group reference: LS…ZBZ/X, Function: Angled actuator, Long, Stainless steel, For use with: For swing doors above 550 mm width

技術規格

General specifications
Product name
Eaton Moeller® series LS Actuator
Part no.
LS-XWA-ZBZ
EAN
4015081065981
Product Length/Depth
33 millimetre
Product height
15 millimetre
Product width
35 millimetre
Product weight
0.012 kilogram
Compliances
CE Marked
Certifications
EN 60947-5
CSA Std. C22.2 No. 14
IEC 60947-5
UL 508
IEC/EN 60947
UL Category Control No.: NKCR
CSA Class No.: 3211-03
UL
IEC/EN 60947-5
CSA-C22.2 No. 14
UL File No.: E29184
CSA File No.: 012528
CSA
CE
Product Tradename
LS
Product Type
Actuator
Product Sub Type
None
Globally Marketable
Yes
Features & Functions
Functions
For combination with LS-...ZBZ/X basic devices
Material
Stainless steel
General information
Duty factor
100 %
Model
Actuator with vertical mounting
Operating frequency
800 Operations/h
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
4000 V AC
Repetition accuracy
0.02 mm (Contacts/switching capacity)
Type
Actuator
Angled actuator
Ambient conditions, mechanical
Mounting position
As required
Shock resistance
10 g, Standard-action contact, Mechanical, Half-Sinusoidal shock 20 ms
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Terminal capacity (flexible with ferrule)
1 x (0.5 - 1.5) mm²
2 x (0.5 - 1.5) mm²
Terminal capacity (solid)
1 x (0.75 - 2.5) mm²
2 x (0.75 - 1.5) mm²
Electrical rating
Power consumption
8 W at 24 V DC (electromechanical actuation)
8 VA at 120 V AC (electromechanical actuation)
Rated insulation voltage (Ui)
400 V
Rated operational current (Ie)
6 A at AC-15, 24 V
3 A at 24 V
0.8 A at 110 V
0.3 A at 220 V
6 A at AC-15, 220 V 230 V 240 V
4 A at AC-15, 380 V 400 V 415 V
Short-circuit protection rating
Max. 6 A gG/gL, Fuse, Contacts
Supply frequency
Max. 400 Hz, Contacts
Voltage tolerance
1.1 x Us, Pick-up and drop-out values
0.85 x Us, Pick-up and drop-out values
Actuator
Mechanical holding force
1200 N (according to GS-ET-19 (04/2004), XNW)
1700 N (according to GS-ET-19 (04/2004), XG, XW, XNG)
1600 N (according to GS-ET-19 (04/2004), XWA, XFG, XF)
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
Not applicable.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

文檔

更多資料

請訪問我們主站的產品頁面了解更多信息。


進一步了解