variable speed drive ATV630 – 250kW/400HP – 380…480V – IP00
variable speed drive ATV630 – 250kW/400HP – 380…480V – IP00
variable speed drive ATV630 – 250kW/400HP – 380…480V – IP00
Download Product Datasheet
Characteristics
range of product
product or component type
product specific application
device short name
variant
product destination
Asynchronous motors
mounting mode
EMC filter
IP degree of protection
IP00 conforming to IEC 60529
IP21 (with kit VW3A9113) conforming to IEC 61800-5-1
IP21 (with kit VW3A9113) conforming to IEC 60529
type of cooling
supply frequency
network number of phases
[Us] rated supply voltage
motor power kW
220 kW (heavy duty)
motor power hp
300 hp heavy duty
line current
366 A at 480 V (normal duty)
365 A at 380 V (heavy duty)
301 A at 480 V (heavy duty)
prospective line Isc
apparent power
229 kVA at 480 V (heavy duty)
continuous output current
387 A at 2.5 kHz for heavy duty
maximum transient current
581 A during 60 s (heavy duty)
asynchronous motor control profile
Constant torque standard
Optimized torque mode
synchronous motor control profile
Synchronous reluctance motor
output frequency
speed drive output frequency
nominal switching frequency
switching frequency
2...8 kHz adjustable
safety function
discrete input logic
communication port protocol
Modbus serial
Ethernet
option card
Slot A: communication module, Profinet
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
output voltage
permissible temporary current boost
1.5 x In during 60 s (heavy duty)
motor slip compensation
Adjustable
Not available in permanent magnet motor law
Can be suppressed
acceleration and deceleration ramps
braking to standstill
protection type
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
frequency resolution
Analog input: 0.012/50 Hz
electrical connection
Line side: screw terminal4 x 185 mm²/3 x 350 kcmil
Motor: screw terminal4 x 185 mm²/3 x 350 kcmil
connector type
RJ45 (on the remote graphic terminal) for Modbus serial
physical interface
transmission frame
transmission rate
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
exchange mode
data format
type of polarization
number of addresses
method of access
supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
local signalling
3 LEDs (dual colour)embedded communication status:
4 LEDs (dual colour)communication module status:
1 LED (red)presence of voltage:
width
height
depth
product weight
analogue input number
analogue input type
AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12 bits
discrete input number
discrete input type
DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
input compatibility
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
discrete input logic
Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1)
Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
analogue output number
analogue output type
Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits
sampling duration
5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
linearity error
AO1, AO2: +/- 0.2 % for analog output
relay output number
relay output type
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time
minimum switching current
maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
isolation
Variable speed drive application selection
Food and beverage processing Other application
Mining mineral and metal Fan
Mining mineral and metal Pump
Oil and gas Fan
Water and waste water Other application
Building - HVAC Screw compressor
Food and beverage processing Pump
Food and beverage processing Fan
Food and beverage processing Atomization
Oil and gas Electro submersible pump (ESP)
Oil and gas Water injection pump
Oil and gas Jet fuel pump
Oil and gas Compressor for refinery
Water and waste water Centrifuge pump
Water and waste water Positive displacement pump
Water and waste water Electro submersible pump (ESP)
Water and waste water Screw pump
Water and waste water Lobe compressor
Water and waste water Screw compressor
Water and waste water Compressor centrifugal
Water and waste water Fan
Water and waste water Conveyor
Water and waste water Mixer
Motor power range AC-3
250…500 kW at 480…500 V 3 phases
insulation resistance
noise level
power dissipation in W
Natural convection: 606 W at 380 V, switching frequency 2.5 kHz
volume of cooling air
operating position
maximum THDI
electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree
vibration resistance
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance
relative humidity
ambient air temperature for operation
40…60 °C (with derating factor)
ambient air temperature for storage
operating altitude
1000...3000 m with current derating 1 % per 100 m
environmental characteristic
Dust pollution resistance class 3S2 conforming to EN/IEC 60721-3-3
standards
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
product certifications
UL
REACH
TÜV
marking
Sustainable offer status
EU RoHS Directive
EU RoHS Declaration
Mercury free
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE