Product Description
off-delay timing relay – 1 s..100 h – 24..240 V AC – 1 OC
Technical Specifications
Download Product Datasheet
Main
range of product |
Zelio Time
|
|
product or component type |
Modular timing relay
|
|
discrete output type |
Relay
|
|
width |
17.5 mm
|
|
device short name |
RE17R
|
|
time delay type |
C
|
|
time delay range |
6...60 s 1...10 h 1...10 min 6...60 min 0.1...1 s 1...10 s 10...100 h
|
|
nominal output current |
8 A
|
|
Complementary
contacts type and composition |
1 C/O
|
|
contacts material |
Cadmium free
|
|
height |
90 mm
|
|
depth |
72 mm
|
|
control type |
Selector switch front panel
|
|
[Us] rated supply voltage |
24...240 V AC 50/60 Hz 24 V DC
|
|
voltage range |
0.85...1.1 Us
|
|
supply frequency |
50...60 Hz +/- 5 %
|
|
release of input voltage |
10 V
|
|
connections - terminals |
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
|
tightening torque |
0.6…1 N.m conforming to IEC 60947-1
|
|
housing material |
Self-extinguishing
|
|
repeat accuracy |
+/- 0.5 % conforming to IEC 61812-1
|
|
temperature drift |
+/- 0.05 %/°C
|
|
voltage drift |
+/- 0.2 %/V
|
|
setting accuracy of time delay |
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
|
|
control signal pulse width |
100 ms with load in parallel typical 30 ms typical
|
|
insulation resistance |
100 MOhm at 500 V DC conforming to IEC 60664-1
|
|
reset time |
120 ms on de-energisation typical
|
|
on-load factor |
100 %
|
|
power consumption in VA |
0…32 VA at 240 V AC
|
|
maximum power consumption in W |
0.6 W at 24 V DC
|
|
minimum switching current |
10 mA at 5 V DC
|
|
maximum switching current |
8 A AC/DC
|
|
maximum switching voltage |
250 V AC
|
|
breaking capacity |
2000 VA
|
|
operating frequency |
10 Hz
|
|
electrical durability |
100000 cycles (8 A at 250 V AC maximum) for resistive load
|
|
mechanical durability |
10000000 cycles
|
|
dielectric strength |
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
|
|
[Uimp] rated impulse withstand voltage |
5 kV during 1.2/50 µs
|
|
power on delay |
100 ms
|
|
marking |
CE
|
|
creepage distance |
4 kV/3 conforming to IEC 60664-1
|
|
safety reliability data |
B10d = 270000 MTTFd = 296.8 years
|
|
mounting position |
Any position in relation to normal vertical mounting plane
|
|
mounting support |
35 mm DIN rail conforming to EN/IEC 60715
|
|
local signalling |
LED indicator for on steady: relay energised, no timing in progress LED indicator for flashing: timing in progress 80 % ON and 20 % OFF LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF
|
|
product weight |
0.07 kg
|
|
time delay type |
C
|
|
functionality |
Off-delay timing
|
|
compatibility code |
RE17
|
|
Environment
immunity to microbreaks |
20 ms
|
|
standards |
EN 61000-6-4 EN 61000-6-2 EN 61000-6-3 2004/108/EC 2006/95/EC IEC 61812-1 EN 61000-6-1
|
|
product certifications |
CULus GL CSA
|
|
ambient air temperature for storage |
-30…60 °C
|
|
ambient air temperature for operation |
-20…60 °C
|
|
IP degree of protection |
IP20 (terminal block) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529
|
|
vibration resistance |
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
|
|
shock resistance |
15 gn for 11 ms conforming to IEC 60068-2-27
|
|
relative humidity |
93 % without condensation conforming to IEC 60068-2-30
|
|
electromagnetic compatibility |
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2 Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5 Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11 Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11 Conducted and radiated emissions: , class B, conforming to EN 55022
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
More Information
Please visit the product page on our main site for more information.
Learn more