Product Description
- Breaking capacity of 50kA, according to EN/IEC standard 60947 – 2, suitable for protection of commercial and middle power installations. Rated insulation voltage of 500V. Rated impulse withstand voltage of 6kV.
- Compliat with NEMA AB‐1. Climatic condition according to IEC/EN 60947 – 1 Annex Q, Cat. F subject to temperature, humidity, vibration, shock and salt mist.
- Protection unit with LCD screen for regulation of thermal and magnetic currents. Thermal protection within range of 0,4 – 1,0 of the rated current. Magnetic protection within range of 1,5 – 10 of the rated current.Equipped with earth leakage module with LCD screen. Earth leakage trip integrated of type A, with adjustable sensitivity of 0,03 ‐ 0,3 ‐ 1 ‐ 3 Ampere and adjustable tripping of 0 ‐ 0,3 ‐ 1 ‐ 3 seconds
- Can be equipped with releases (undervoltage and shunt releases) and auxiliary contacts. Can used with rotary handles or motor operator. Locking accessories are available.
- Has diffent type of possible connection accessories: cage terminals, spreader and rear terminals. Is available also in a plug-in version (circuit breaker fitted with special terminals and mounted on a plug-in base)
The + product
- DPX3 platform has been developed to give a new solution of protection devices for a more precise approach in “flux” installations in order to offer the correct answer little panel builders or installers.
- DPX3 platform provide a complete “flux” approach in premium market segment, for usually reduced value projects and a Fit & Forget approach offering direct sale distribution