産品概述
control unit Micrologic 2.0 A, for Masterpact NT/NW, LI protections
技術規格
Download Product Datasheet
Main
range |
Masterpact
|
|
product name |
Micrologic
|
|
product or component type |
Control unit
|
|
range compatibility |
Masterpact NT06...16 Masterpact NW08...40 Masterpact NW40b...63
|
|
device application |
Distribution
|
|
poles description |
4P 3P
|
|
protected poles description |
4t 3t 3t + N/2
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
trip unit name |
Micrologic 2.0 A
|
|
trip unit technology |
Electronic
|
|
trip unit protection functions |
Basic protection
|
|
protection type |
Overload protection (long time) Instantaneous short-circuit protection
|
|
trip unit rating |
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
|
|
Complementary
mounting mode |
Fixed Drawout
|
|
long time pick-up adjustment type Ir |
Adjustable 9 settings
|
|
long time pick-up adjustment range |
0.4...1 x In
|
|
long time delay adjustment type |
Adjustable 9 settings
|
|
[tr] long-time delay adjustment range |
0.7…16.6 s 7.2 x Ir 0.7…24 s 6 x Ir 12.5…600 s 1.5 x Ir
|
|
thermal memory |
20 mn
|
|
instantaneous pick-up adjustment type Ii |
Adjustable 9 settings
|
|
instantaneous pick-up adjustment range |
1.5...10 x Ir
|
|
zone selective interlocking ZSI |
With
|
|
communication of data |
Measurement readout Protection and alarm settings
|
|
display type |
Digital display
|
|
type of measurement |
Ammeter
|
|
Environment
ambient air temperature for operation |
-25…70 °C
|
|
ambient air temperature for storage |
-25…85 °C
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
Contractual warranty
Warranty |
18 months
|
|