産品概述
compact smart relay Zelio Logic – 20 I O – 100..240 V AC – clock – display
技術規格
Download Product Datasheet
Main
range of product |
Zelio Logic
|
|
product or component type |
Compact smart relay
|
|
Complementary
local display |
With
|
|
number or control scheme lines |
0…240 with ladder programming 0…500 with FBD programming
|
|
cycle time |
6…90 ms
|
|
backup time |
10 years at 25 °C
|
|
clock drift |
12 min/year at 0…55 °C 6 s/month at 25 °C
|
|
checks |
Program memory on each power up
|
|
[Us] rated supply voltage |
100...240 V AC
|
|
supply voltage limits |
85…264 V
|
|
supply frequency |
50/60 Hz
|
|
maximum supply current |
100 mA at 100 V (without extension) 50 mA at 240 V (without extension)
|
|
power consumption in VA |
11 VA without extension
|
|
isolation voltage |
1780 V
|
|
protection type |
Against inversion of terminals (control instructions not executed)
|
|
discrete input number |
12
|
|
discrete input voltage |
100...240 V AC
|
|
discrete input current |
0.6 mA
|
|
discrete input frequency |
57...63 Hz 47...53 Hz
|
|
voltage state 1 guaranteed |
>= 79 V for discrete input
|
|
voltage state 0 guaranteed |
<= 40 V for discrete input
|
|
current state 1 guaranteed |
>= 0.17 mA (discrete input)
|
|
current state 0 guaranteed |
<= 0.5 mA (discrete input)
|
|
input impedance |
350 kOhm for discrete input
|
|
number of outputs |
8 relay
|
|
output voltage limits |
5...30 V DC (relay output) 24...250 V AC
|
|
contacts type and composition |
NO for relay output
|
|
output thermal current |
8 A for all 8 outputs for relay output
|
|
electrical durability |
AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1 DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
|
|
switching capacity in mA |
>= 10 mA at 12 V (relay output)
|
|
operating rate in Hz |
0.1 Hz (at Ie) for relay output 10 Hz (no load) for relay output
|
|
mechanical durability |
10000000 cycles for relay output
|
|
[Uimp] rated impulse withstand voltage |
EN/IEC 60947-1 and EN/IEC 60664-1 4 kV
|
|
clock |
With
|
|
response time |
50 ms with ladder programming (from state 0 to state 1) for discrete input 50 ms with ladder programming (from state 1 to state 0) for discrete input 50...255 ms with FBD programming (from state 0 to state 1) for discrete input 50...255 ms with FBD programming (from state 1 to state 0) for discrete input 10 ms (from state 0 to state 1) for relay output 5 ms (from state 1 to state 0) for relay output
|
|
connections - terminals |
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
|
|
tightening torque |
0.5 N.m
|
|
overvoltage category |
III conforming to EN/IEC 60664-1
|
|
product weight |
0.38 kg
|
|
Environment
immunity to microbreaks |
1 ms
|
|
product certifications |
C-Tick CSA GL GOST UL
|
|
standards |
EN/IEC 61000-4-6 level 3 EN/IEC 61000-4-11 EN/IEC 60068-2-27 Ea EN/IEC 61000-4-5 EN/IEC 60068-2-6 Fc EN/IEC 61000-4-12 EN/IEC 61000-4-2 level 3 EN/IEC 61000-4-3 EN/IEC 61000-4-4 level 3
|
|
IP degree of protection |
IP20 (terminal block) conforming to IEC 60529 IP40 (front panel) conforming to IEC 60529
|
|
environmental characteristic |
EMC directive conforming to EN/IEC 61000-6-2 EMC directive conforming to EN/IEC 61000-6-3 EMC directive conforming to EN/IEC 61000-6-4 EMC directive conforming to EN/IEC 61131-2 zone B Low voltage directive conforming to EN/IEC 61131-2
|
|
disturbance radiated/conducted |
Class B conforming to EN 55022-11 group 1
|
|
pollution degree |
2 conforming to EN/IEC 61131-2
|
|
ambient air temperature for operation |
-20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2 -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
|
|
ambient air temperature for storage |
-40…70 °C
|
|
operating altitude |
2000 m
|
|
maximum altitude transport |
3048 m
|
|
relative humidity |
95 % without condensation or dripping water
|
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
REACh Regulation |
|
|
EU RoHS Directive |
|
|
Mercury free |
Yes
|
|
RoHS exemption information |
|
|
China RoHS Regulation |
|
|
Environmental Disclosure |
|
|
Circularity Profile |
|
|
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
|
Contractual warranty
Warranty |
18 months
|
|