偵測器&變流器

CT-1/210

零相變流器CT-1/210 φ210mm

加入詢價單

産品概述

Core Balance Current Transformer CT-1/210 (CBCT) allow to sense the leaking currents to earth . These transformers have been designed to be coupled to the earth leakage current relays which can be used to generate the tripping signal . All active wires (phase and neutral) of the three phase or single phase lines should pass through the internal core of the transformers . The net resultant flux being zero does not induce any current in the secondary of the transformer. Thus the secondary current of the core balance current transformer when all the three phases are healthy is zero . When an earth fault occurs in one of the phases, the zero-sequence fault current which flows is not cancelled by the flux of the other two phases and hence induces a current in the secondary.

技術規格

Dimention : 210 mm(Core diameter) Mounting type : DIN rail IP : IP20 Measured Quantity : leaking currents to earth Approximate Weight : 1450 g Core : Solid core Min. Meas. Current : 250mA Mounting type : On plate

文檔

更多資料

請訪問我們主站的產品頁面了解更多信息。


進一步了解